Modbus TCP
Build Modbus TCP request and response frames with a correct 7-byte MBAP header, and parse captured TCP frames.
TCP request generator
TCP response generator
TCP parser
How to use the Modbus TCP tool
Generate a TCP request
Set the transaction ID (0–65535), unit ID, function code, start address and quantity, then click Generate TCP request. The tool builds a 7-byte MBAP header followed by the function code and data. The transaction ID is echoed back by the server in its response. Example: 00 01 00 00 00 06 01 03 00 00 00 02 reads two holding registers from address 0.
MBAP header fields
The MBAP header is 7 bytes: 2-byte transaction ID, 2-byte protocol ID (must be 0x0000), 2-byte length (total bytes of unit ID + PDU) and 1-byte unit ID. Modbus TCP carries no CRC-16 — the length field verifies the frame.
Generate a response
Match the function code of your request, choose a data type and byte order, enter the decimal value, and click Generate TCP response. The response reuses the request's transaction ID and unit ID, and the MBAP length is computed from the content. Example: 00 01 00 00 00 07 01 03 04 00 01 00 02.
Parse a captured frame
Paste a TCP frame and click Parse frame. The tool decodes the transaction ID, protocol ID, length, unit ID, function code and PDU data. Verify the protocol ID is 0 and the length equals the unit ID plus the PDU byte count.